Standards & Specifications Cross-Reference Matrix

No single standard governs an AI data center. Six overlapping regimes do (resilience, electrical installation and safety, thermal, efficiency, hardware and compliance), and they do not map one-to-one. Use this index to pick the exact source text for a contract, RFP or commissioning script.

What you'll decide here

  1. Name the exact document: issuer, part, edition, status and what it covers. A committee or class name alone does not identify one.
  2. Pick Uptime, TIA or EN/ISO maintenance and fault requirements before you commit to a rating. Equal numerals do not make the schemes equivalent.
  3. Choose documents by what they cover: TC 9.9 for thermal classes, and separate documents for the open rack, the power shelf and the cooling loop.
  4. Check the publisher's record before contract freeze. Contract to the issued edition; a superseded one needs a contractual reason.
  5. Go to the specialist chapters for how to apply each document. Appendix A and /library list the same documents.

This appendix indexes the standards the guide relies on most. Each row tells you who publishes the document, which edition is current, what it covers, and where to open the publisher's record. A row is an index entry, not an endorsement. The PNNL/ASHRAE/NEMA AI Data Center Energy Performance Framework, for example, gives lifecycle guidance rather than mandatory requirements, and a UEC publication does not prove that two devices interoperate. Put the issued edition in the contract. A draft is a risk you are buying, because its clauses can still change after you design to them.

1. Facility standards and classification documents

Uptime Tier, TIA Rated and EN/ISO Availability Classes differ in scope and tests, and matching numerals do not make them equivalent. Decide which maintenance and fault outcomes you need in Chapter 12.1 before a rating becomes contractual.

Document identity index: facility requirements
DocumentKindIssuing bodyPart / edition / versionStatusAs ofAccessApplicable boundaryEvidence locator
ANSI/TIA-942-CstandardTIAC (2024)current2026-09-05paidFacility infrastructure and Rated levels.↗ · Claim
ANSI/TIA-942-C AI addendumstandardTIATIA-942-C-1 (Addendum 1: AI); call for interest 2026-02-26draft2026-10-16unpublishedAI facility cabling, power and cooling.↗
ANSI/BICSI 002standardBICSI2024current2026-09-05paidFacility design.↗
ANSI/BICSI 009standardBICSI2024current2026-09-05paidFacility operations.↗
Uptime Tier Standard: TopologystandardUptime Instituteedition not stated onlinecurrent2026-09-05freeFacility topology outcomes.↗
Uptime Tier Standard: Operational SustainabilitystandardUptime Instituteeffective 2013-04-01current2026-09-05freeFacility management behaviors.↗
EN 50600-1standardCENELEC / BSI2019current2026-09-05paidFacility classification.↗
EN 50600-2-4standardCENELEC / BSI2023current2026-09-05paidTelecom cabling.↗
EN 50600-3-1standardCENELEC / BSI2026current2026-09-05paidManagement and operation.↗
ISO/IEC 22237-1standardISO/IEC2021current2026-09-05paidFacility classification.↗
ISO/IEC 22237-2standardISO/IEC2024current2026-09-05paidBuilding construction.↗
ISO/IEC 22237-3standardISO/IEC2021current2026-09-05paidPower distribution.↗
ISO/IEC 22237-4standardISO/IEC2021current2026-09-05paidEnvironmental control.↗
ISO/IEC TS 22237-5specificationISO/IEC2018current2026-09-05paidTelecom cabling.↗
ISO/IEC 22237-6standardISO/IEC2024current2026-09-05paidPhysical security.↗
ISO/IEC TS 22237-7specificationISO/IEC2018current2026-09-05paidManagement and operation.↗
EN 50600-2-1standardCENELEC / BSI2021current2026-09-05paidBuilding construction.↗
EN 50600-2-2standardCENELEC / BSI2019current2026-09-05paidPower supply and distribution.↗
EN 50600-2-3standardCENELEC / BSI2019current2026-09-05paidEnvironmental control.↗
EN 50600-2-5standardCENELEC / BSI2021current2026-09-05paidPhysical security.↗
NERC CIP-014standardNERC / FERC-3 in force; -4 approved 2026-09-10, effective 2028-10-01current2026-10-16freePhysical security of transmission substations; a Transmission Owner/Operator duty (Chapter 4.3).↗
NERC CLO-001-1, CLO-002-1, CLO-003-1 (Project 2026-02)standardNERC / FERC-1 final-ballot texts (October 2026); FAC-001-5 and FAC-002-5 revised alongsidedraft2026-10-19freeComputational Load Sites ≥50 MW at ≥100 kV: interconnection, modeling, data, protection, disturbance monitoring; no ride-through curve. Ballot passed 2026-10-15 (Chapter 4.3).↗
OCP Interface Specification Between Hyperscalers and Utility Grid for Disturbance PerformancespecificationOCP1.0.0 (effective 2026-09-17)current2026-10-19freeRide-through and recovery for computing load only; cooling exempt. An industry spec, not a regulation: in the US, ERCOT NOGRR282 and SPP rules bind (Chapter 4.10; tests: 13.6).↗
OCP Open Data Center: Next-Generation ML Infrastructure Design PrinciplesspecificationOCP (AMD, Google, Meta, NVIDIA)Revision 0.7.0 (effective 2026-08-27)current2026-10-19freeDesign targets for 2027–28 ML halls: 8,000 lb rack, 12 ft transport aisle, 25 kW/ft average (15 kW/ft air plus 25 kW/ft liquid capacity), 350 kW/ft peak (Chapter 6.1).↗
ERCOT NOGRR282 (Large Computational Load ride-through)regulationERCOT / PUCTPUCT-approved 2026-07-09; effective 2026-08-01current2026-10-19freeNew Large Computational Loads ≥75 MW (≥50% power electronic): ≥90% of load back within 2 s of voltage above 0.90 pu; operating or approved by 2025-11-14 exempt (Chapter 4.10).↗ · Claim
SPP RR696 High Impact Large Load (HILL) requirementsregulationSPP / FERCRR696 (revision 2025-09-23); applies to requests from 2026-01-15current2026-10-19freeLoads ≥10 MW at ≤69 kV or ≥50 MW above: ride through 0.50–<0.80 pu for 0.50 s, ≥90% recovery within 1 s, at least six fault-clearing attempts in 90 s (Chapter 4.10).↗ · Claim
EirGrid Grid Code modification MPID 345 (demand fault ride-through)regulationEirGrid / CRUCRU decision 2026-09-22; in force from about 2026-10-27current2026-10-19freeTransmission-connected demand: fault ride-through, ±1 Hz/s RoCoF withstand, active-power recovery; non-compliance without a derogation breaches the Code (Chapter 3.2).↗
NERC CLO/CLOP registry criteria (Rules of Procedure Appendices 2, 5A and 5B)regulationNERC / FERCBoard-approved 2026-10-08; FERC filing due 2026-12-31draft2026-10-19freeRegisters Computational Load Owners and Operators for sites ≥50 MW connected at ≥100 kV; a proposal until FERC approves it (Chapter 4.3).↗ · Claim
NERC Level 3 alert: computational loadsguidelineNERCLevel 3 Essential Actions alert (2026-05-04)current2026-10-19freeSeven essential actions for planners, transmission entities, balancing authorities and reliability coordinators; not mandatory, nothing set on data centers directly (Chapter 4.10).↗ · Claim
Status describes publication, not local adoption or compliance. For a document family, pick a specific part: base and SER-pack dates do not date every part. Access refers to the full document, and previews may be free. Work to the boundary in each row. The ↗ link opens the publisher record, and you need access to read paid clauses.

2. Thermal guidance, installation and safety documents

ASHRAE classes define equipment operating ranges, not rack-power ceilings. Chapter 5.1 sets out the limits of air cooling. Chapter 5.7 weighs the economizer and reuse benefits of warmer water against chip thermal margin.

Document identity index: thermal references
DocumentKindIssuing bodyPart / edition / versionStatusAs ofAccessApplicable boundaryEvidence locator
ASHRAE TC 9.9 Datacom EncyclopediaguidelineASHRAEOnline; revision ID not publishedcurrent2026-09-05paidDatacom engineering reference.↗
ASHRAE Datacom book 1: Thermal Guidelines for Data Processing EnvironmentsguidelineASHRAE5th (2021)current2026-10-19paidAir A1–A4/H1 and facility-water W classes.↗ · Access · Claim
ASHRAE Datacom book 2: IT Equipment Power TrendsguidelineASHRAE3rd (2018)historical2026-09-05paidIT power trends.↗ · Access
ASHRAE Datacom book 3: Design Considerations for Datacom Equipment CentersguidelineASHRAE2nd (2009)historical2026-09-05paidFacility design.↗ · Access
ASHRAE Datacom book 4: Liquid Cooling Guidelines for Datacom Equipment CentersguidelineASHRAE2nd (2013)historical2026-09-05paidLiquid-cooling system design.↗ · Access · Errata
ASHRAE Datacom book 5: Structural and Vibration Guidelines for Datacom Equipment CentersguidelineASHRAE2008current2026-09-05paidStructure and vibration.↗ · Access
ASHRAE Datacom book 6: Best Practices for Datacom Facility Energy EfficiencyguidelineASHRAE2nd (2009)historical2026-09-05paidFacility efficiency.↗ · Access
ASHRAE Datacom book 7: High Density Data Centers—Case Studies and Other ConsiderationsguidelineASHRAE2008historical2026-09-05paidHigh-density design cases.↗ · Access
ASHRAE Datacom book 8: Particulate and Gaseous Contamination in Datacom EnvironmentsguidelineASHRAE2nd (2014)current2026-09-05paidContamination control.↗ · Access
ASHRAE Datacom book 9: Real-Time Energy Consumption Measurements in Data CentersguidelineASHRAE2010current2026-09-05paidEnergy measurement.↗ · Access
ASHRAE Datacom book 10: Green Tips for Data CentersguidelineASHRAE2011current2026-09-05paidEfficiency practices.↗ · Access
ASHRAE Datacom book 11: PUE: A Comprehensive Examination of the MetricguidelineASHRAE2014current2026-09-05paidPUE interpretation.↗ · Access
ASHRAE Datacom book 12: Server Efficiency: Metrics for Computer Servers and StorageguidelineASHRAE2015historical2026-09-05paidIT efficiency metrics.↗ · Access
ASHRAE Datacom book 13: IT Equipment Design Impact on Data Center SolutionsguidelineASHRAE2016current2026-09-05paidIT and facility interfaces.↗ · Access
ASHRAE Datacom book 14: Advancing DCIM with IT Equipment IntegrationguidelineASHRAE2019current2026-09-05paidDCIM integration.↗ · Access
ASHRAE Standard 90.1standardASHRAE / IES2025current2026-10-19paidBuilding energy code floor, including minimum chiller efficiencies; data-center IT energy performance falls under Standard 90.4.↗
ASHRAE Standard 90.4standardASHRAE2025current2026-09-05paidData-center energy performance.↗
ASHRAE Standard 127standardASHRAE2020 + Addendum b (approved 2026-02-27)current2026-10-16paidLaboratory rating tests for data-center cooling equipment. Addendum b adds a rating method for liquid-to-liquid CDUs (Chapter 5.6).↗
ASHRAE Standard 188standardASHRAE2021current2026-09-05paidBuilding-water Legionella risk.↗
ASHRAE Standard 202standardASHRAE2024current2026-09-05paidBuilding commissioning process.↗
AI Data Center Energy Performance FrameworkguidelinePNNL / ASHRAE / NEMAOnline; revision ID not publishedcurrent2026-09-05freeAI facility energy and water practices.↗
OCP White Paper: Thermal Boundaries in AI InfrastructurereportOCP (Cooling Environments)v1.00 (2026-10-12)current2026-10-17freeCooling-method selection by efficiency, economics and physics limits; projects a single-phase cold-plate limit near 4,000 W per reticle-class die (Chapter 5.1).↗ · Claim
OCP OAI System Liquid Cooling GuidelinesguidelineOCP (Open Accelerator Infrastructure)2023-03-03 updatecurrent2026-10-19freeCold-plate loop design for 8-OAM training systems: 7.5–12 °C coolant rise, about 1.25–2.0 L/min per kW with PG25 (§1.3). A TCS guideline, not a facility-water target (Chapter 5.6).↗ · Claim
OCP Seizing Data Center Heat Reuse Opportunities: Guidelines for Local AuthoritiesguidelineOCP (Cooling Environments, Heat Reuse sub-project)V 1.00 (September 2024); restated on OCP's blog 2026-05-20current2026-10-17freeLocal-government levers for heat reuse: matching heat users, incentives, agreements before permit approval (Chapter 15.5).↗
ASHRAE Guideline 0guidelineASHRAE2019current2026-09-05paidWhole-building commissioning.↗
ASHRAE Guideline 1.1guidelineASHRAE2025current2026-09-05paidHVAC commissioning.↗
ASHRAE Guideline 12guidelineASHRAE2023current2026-09-05paidBuilding-water Legionella management.↗
ASHRAE Handbook—Fundamentals (2017), Chapter 8guidelineASHRAE2017 SI; Sound and Vibrationhistorical2026-09-08freeOctave/A-weighting, level summation and propagation; no project noise limits.Chapter
ASHRAE labels a book historical once it moves into the paid Datacom Encyclopedia archive; the content is not withdrawn. Thermal Guidelines, 5th edition (2021), is marked current here because it is still the newest edition and defines the A1–A4, H1 and W classes the guide uses. Books not yet migrated are sold separately.
Document identity index: installation and safety references
DocumentKindIssuing bodyPart / edition / versionStatusAs ofAccessApplicable boundaryEvidence locator
NFPA 70standardNFPA2026current2026-09-05paidElectrical installations.↗
NFPA 70EstandardNFPA2027current2026-09-05paidElectrical work safety.↗
NFPA 75standardNFPA2024current2026-09-05paidIT equipment fire protection.↗
NFPA 76standardNFPA2024current2026-09-05paidTelecom facility fire protection.↗
NFPA 72standardNFPA2025current2026-10-19paidFire alarm and signaling: detection, notification and the alarm path (Chapter 6.5).↗
NFPA 13standardNFPA2025current2026-10-19paidSprinkler system installation, including pre-action systems (Chapter 6.5).↗
NFPA 2001standardNFPA2025current2026-10-19paidClean-agent fire extinguishing systems (Chapter 6.5).↗
NFPA 1standardNFPA2027current2026-10-19paidFire Code adopted in some states instead of the IFC; carries the ESS requirements there (Chapter 6.5).↗
International Fire Code (IFC)standardInternational Code Council (ICC)2027 (Section 1207 Electrical Energy Storage Systems); 2024 or 2021 edition where adopted; Section 1206 in 2018-edition statescurrent2026-10-19freeUS model fire code that gives ESS rules legal force where adopted: Section 1207 sets the stored-energy thresholds and recognizes UL 9540A testing (Chapter 6.5).↗
NFPA 855standardNFPA2026current2026-09-05paidStationary energy-storage installation.↗
NFPA 110standardNFPA2025current2026-09-05paidEmergency and standby power systems.↗
NFPA 37standardNFPA2024current2026-10-19paidInstallation and use of stationary combustion engines and gas turbines (Chapter 4.9).↗
NFPA 56standardNFPA2027current2026-10-19paidCleaning and purging of flammable-gas piping, new or existing; forbids using flammable gas to clean pipe (Chapter 4.9).↗
NFPA 59AstandardNFPA2026current2026-10-19paidProduction, storage and handling of LNG; thermal-radiation and vapor-dispersion siting distances, as adopted by the state or local fire code (Chapter 4.9).↗
NFPA 70BstandardNFPA2026current2026-10-16paidElectrical equipment maintenance programs.↗
NFPA 780standardNFPA2026current2026-09-05paidLightning-protection installation.↗
IEC 60038standardIEC2009 + AMD1:2021; ed. 7.1current2026-09-05paidSystem voltage values.↗
IEC 60255standardIECSeries; -1:2022 basevaries by part2026-09-05paidProtection relays.↗
IEC 60309standardIECSeries; -1:2021 + COR1:2023 basevaries by part2026-09-05paidIndustrial plugs and sockets.↗
IEC 60320standardIECSeries; -1:2021 basevaries by part2026-09-05paidEquipment couplers.↗
IEC 60364standardIECSeries; -1:2025 basevaries by part2026-10-19paidLow-voltage installations. Europe applies the parts as the CENELEC HD 60364 series, through each country's national standards.↗
BS 7671standardIET / BSI2018+A4:2026 (published April 2026); A2:2022+A3:2024 withdrawn 2026-10-15current2026-10-19paidUK wiring regulations; Amendment 4 adds rules for battery energy storage and ICT functional earthing (Appendix G).↗ · Claim
CSA C22.1 (Canadian Electrical Code, Part I)standardCSA Group2024 (26th edition)current2026-10-19paidCanadian electrical installation code, adopted and amended by each province or territory (Appendix G).↗
AS/NZS 3000 (Wiring Rules)standardStandards Australia / Standards New Zealand2018 + Amd 1:2020, Amd 2:2021, Amd 3:2023current2026-10-19paidAustralian and New Zealand electrical installation rules, applied through state, territory and national law (Appendix G).↗
NR-10regulationBrazil Ministry of Labour and EmploymentAs amended by Portaria SEPRT 915/2019 (in force until 2027-05-31); new text by Portaria MTE 737/2026 in force from 2027-06-01current2026-10-19freeSafety in electrical installations and services (electrical work safety) (Appendix G).↗
IEC 61000-4-7standardIEC2002 + AMD1:2008 (consolidated 2.1)current2026-10-13paidHarmonic and interharmonic measurement method.↗
IEC 61000-4-30standardIEC2025; corrected 2026-07current2026-09-05paidPower-quality measurement.↗
IEC 62368-1standardIEC4.0 (2023; corrected 2025-08)current2026-10-13paidSafety of ICT and audio/video equipment, including energy-source classes.↗
IEC 61439standardIECSeries; -1:2020 basevaries by part2026-09-05paidLow-voltage assemblies.↗
IEC 61508-6standardIEC2010; ed. 2.0current2026-09-05paidFunctional-safety application guidance.↗
IEC 61511standardIEC2026 SER pack; part editions varyvaries by part2026-09-05paidProcess safety systems.↗
IEC 61643standardIECSeries; -01:2024 basevaries by part2026-09-05paidSurge-protective devices.↗
IEC 61643-01standardIEC2024; ed. 1.0current2026-09-05paidSurge-protection general requirements.↗
IEC 61643-11standardIEC2025; ed. 2.0current2026-09-05paidAC surge-protective devices.↗
IEC 61643-41standardIEC2025; ed. 1.0current2026-09-05paidDC surge-protective devices.↗
IEC 61850standardIEC2026 SER pack; part editions varyvaries by part2026-09-05paidUtility-automation communications.↗
IEC 62040-3standardIEC2021; ed. 3.0current2026-10-19paidUPS performance and test methods, including the VFI/VI/VFD classification used to compare double-conversion and eco modes (Chapter 4.5).↗
IEC 62053-22standardIEC2020; ed. 2.0current2026-09-05paidStatic active-energy meters.↗
IEC 62271standardIEC2026 SER pack; part editions varyvaries by part2026-09-05paidHigh-voltage switchgear.↗
IEC 62305standardIEC2026 SER pack; parts 1–4:2024varies by part2026-09-05paidLightning protection.↗
IEC 62305-2standardIEC2024 + COR1:2024; ed. 3.0current2026-09-05paidLightning-risk management.↗
IEC 62305-3standardIEC2024; ed. 3.0current2026-09-05paidPhysical lightning protection.↗
IEC 62682standardIEC2022; ed. 2.0current2026-09-05paidAlarm-system management.↗
EN 54standardCEN / BSISeries; -1:2021 introductionvaries by part2026-09-05paidFire detection and alarms.↗
EN 13445standardCEN / BSISeries; -1:2026 generalvaries by part2026-09-05paidUnfired pressure vessels.↗
EN 13480standardCEN / BSISeries; -1:2024 generalvaries by part2026-09-05paidMetallic industrial piping.↗
ASME B31.3standardASME2024current2026-10-19paidProcess piping: design, materials, fabrication, examination and pressure testing (Chapter 5.13).↗
ASME B31.5standardASME2022current2026-10-19paidRefrigeration piping and heat-transfer components (Chapter 5.13).↗
ASME B31.9standardASME2025current2026-10-19paidBuilding services piping, such as chilled- and condenser-water systems in commercial and institutional buildings, within its size, pressure and temperature limits (Chapter 5.13).↗
Pressure Equipment Directive (PED)regulationEUDirective 2014/68/EU (consolidated text 2026-05-30)current2026-10-19freeEU conformity assessment for pressure equipment and assemblies above 0.5 bar, graded into Categories I–IV (Chapter 5.13).↗ · Claim
EN 15978standardCEN / BSI2026current2026-09-05paidBuilding environmental assessment.↗
EN 16750standardCEN / NSAI2017 + A1:2020current2026-09-05paidOxygen-reduction fire prevention.↗
ETSI EN 300 132-3-1standardETSIV2.1.1 (2012-02); replaced by Part 3 V2.3.1 (2023)superseded2026-09-30freeDC power interface up to 400 V at telecom/ICT equipment input.↗
ISO 668standardISO2020 + Amd1:2022current2026-09-05paidFreight-container dimensions.↗
ISO 1996-2standardISO2017 (Edition 3)current2026-10-16paidEnvironmental noise: determining sound pressure levels; informative Annex K gives an objective tonal screen.↗
ISO 8528-5standardISO2025current2026-10-16paidGenerator-set performance classes and load-step response.↗
ISO 10816standardISOSeries; editions vary by partvaries by part2026-10-19paidMachine vibration evaluation. Parts 1 to 5 are withdrawn and replaced by the matching ISO 20816 parts, so specify ISO 20816 where a part exists; the pump part (2009) stands.↗
ISO 14001standardISO2026; ed. 4current2026-09-05paidEnvironmental management.↗
ISO 14040standardISO2006 + Amd1:2020current2026-09-05paidLife-cycle assessment.↗
ISO 14067standardISO2018; second edition in development (ISO/WD 14067.2)current2026-10-16paidProduct carbon footprint (quantification and communication); how IT-equipment footprints are assessed outside a building LCA.↗
ISO 14520standardISOPart 1: 2023 (ed. 4); agent parts dated separately (e.g. Part 5: 2024, Part 17: 2022)varies by part2026-10-19paidGaseous (clean-agent) fire-extinguishing systems: design and installation; the international counterpart of NFPA 2001 (Chapter 6.5).↗
ISO/IEC 17025standardISO/IEC2017current2026-10-16paidTesting and calibration laboratory competence.↗
ISO 45001standardISO2018 + Amd1:2024current2026-09-05paidOccupational health and safety.↗
ANSI/TIA-607standardTIAE (2024)current2026-09-05paidTelecom bonding and grounding.↗
IEEE 80standardIEEE2013; incorporates Cor1:2015inactive-reserved2026-09-05paidSubstation grounding.↗
IEEE 81guidelineIEEE2025 (supersedes IEEE 81-2012)current2026-10-19paidGuide for measuring earth resistivity, ground impedance and earth surface potentials of a grounding system (Wenner four-pin surveys for grid design) (Chapter 4.11).↗
IEEE 1100standardIEEE2005inactive-reserved2026-09-05paidEquipment powering and grounding.↗
IEEE 142standardIEEE2007inactive-reserved2026-09-05paidIndustrial grounding.↗
IEEE 3003.1standardIEEE2019current2026-10-13paidGrounding of industrial and commercial power systems.↗
IEEE 1547standardIEEE2018 + 1547a:2020current2026-09-05paidDistributed-energy interconnection.↗
IEEE 1668recommended practiceIEEE2017active2026-09-09paidVoltage-sag and short-interruption ride-through testing for end-use equipment below 1,000 V; the ride-through curve SPP's HILL requirement builds on (Chapter 4.10).↗
IEEE 1584standardIEEE2018current2026-09-05paidArc-flash calculations.↗
IEEE 2030.7standardIEEE2017current2026-09-05paidMicrogrid controllers.↗
IEEE 2030.8standardIEEE2018current2026-09-05paidMicrogrid-controller tests.↗
IEEE 242standardIEEE2001inactive-reserved2026-09-05paidIndustrial protection.↗
IEEE 2800standardIEEE2022current2026-09-05paidTransmission-connected inverter resources.↗
IEEE 2883standardIEEE2022current2026-09-05paidStorage sanitization.↗
IEEE 2883.1recommended practiceIEEE2025active2026-10-16paidApplying IEEE 2883 sanitization methods across provisioning, reuse, resale and disposal.↗
IEEE 3002.2standardIEEE2018current2026-09-05paidLoad-flow studies.↗
IEEE 3002.3standardIEEE2018current2026-09-05paidShort-circuit studies.↗
IEEE 3004standardIEEESeries; editions vary by partvaries by part2026-09-05paidEquipment protection.↗
IEEE 399standardIEEE1997inactive-reserved2026-09-05paidIndustrial power-system analysis.↗
IEEE 450standardIEEE2020current2026-09-05paidStationary lead-acid battery maintenance.↗
IEEE 1188recommended practiceIEEE2025active2026-10-16paidVRLA battery maintenance and testing.↗
IEEE 519standardIEEE2022current2026-09-05paidHarmonic control.↗
IEEE C57.110recommended practiceIEEE2018active2026-09-08paidTransformer capability under nonsinusoidal currents; apply its method to the transformer you are offered.↗
IEEE PC57.110revision projectIEEEPAR approved 2026-02-12active PAR; not a published replacement2026-09-08unpublishedTwo-winding transformer scope; excludes rectifier transformers per the public project description. Draft clauses are not public.Project
IEEE P80guidelineIEEEPAR 2025-09-10; draft ID not publicdraft2026-09-05unpublishedSubstation grounding revision.↗
ISO 20816standardISOSeries; Part 1:2016varies by part2026-09-08paidMachine vibration; select machinery part. Excludes floor/pipe-support limits.Catalog
ANSI/TIA-568standardTIAPart 3 revision E (568.3-E)current2026-10-16paidStructured cabling; 568.3 covers optical fiber components and polarity methods A, B, C, U1 and U2.↗
UL 9540AstandardUL Standards & Engagement6th ed. (2026-03-13)current2026-10-16paidThermal-runaway fire test for BESS, including the large-scale fire test (Chapter 6.5).↗
UL 9540standardUL Standards & Engagement3rd ed. (2023-06-28); revised 2025-03-07current2026-10-19paidSafety listing of a complete energy-storage system. A UL 9540A fire-test report is not a UL 9540 listing (Chapter 6.5).↗
UL 1449standardUL Standards & Engagement5th ed. (2021); ANSI-approved revision 2025-10-21current2026-10-19paidNorth American surge-protective device standard. Its scope names AC and PV DC applications, so a non-PV 800 VDC SPD needs its own evaluation (Chapter 4.11).↗ · Claim
UL 2877specificationUL LLC (UL Solutions)Outline of Investigation (Power Supplies, Medium Voltage); certification program launched 2026-09-24current2026-10-19paidPower supplies with input above 1,000 V up to 38 kV; the basis for certifying medium-voltage solid-state power units. No certified product was named at launch (Chapter 4.7).↗
UL 4501specificationUL LLC (UL Solutions)Outline of Investigation; certification program launched 2026-09-29current2026-10-19paidDirect-to-chip liquid-cooling parts (cold plates, manifolds, quick disconnects): coolant compatibility, pressure, leak integrity, durability, flow, interoperability (Chapter 5.11).↗
UL 2140specificationUL LLC (UL Solutions)Outline of Investigation, Edition 1 (2026-08-31)current2026-10-19paidFactory-built prefabricated power-distribution assemblies, certified as a whole with factory follow-up (Chapter 6.4).↗
OCP White Paper: Requirements for Energy Storage Systems Used in Data CentersreportOCP (Data Center Facility, Energy sub-project; OCP Ready)Rev 1.0, Version 1.0 (January 2026)current2026-10-17freeData-center ESS requirements: BESS testing, detection, suppression, ventilation, lithium handling (Chapter 4.5; fire code in Chapter 6.5).↗
49 CFR Part 192regulationUS DOT PHMSAcurrent eCFRcurrent2026-10-19freeTransportation of natural gas by pipeline: minimum federal safety standards; usually governs the operator's lateral and meter station (Chapter 4.9).↗
49 CFR Part 193regulationUS DOT PHMSAcurrent eCFRcurrent2026-10-19freeLNG facilities that are part of a gas pipeline system; excludes LNG facilities used by an ultimate consumer (Chapter 4.9).↗

3. Efficiency metric documents

A sustainability filing needs the ISO/IEC 30134 part, edition and measurement boundary that apply to it. Chapter 15.1 derives the metrics, and this appendix gives their source texts. The nine-part ISO/IEC 30134 family is indexed below.

Document identity index: efficiency metrics
DocumentKindIssuing bodyPart / edition / versionStatusAs ofAccessApplicable boundaryEvidence locator
ISO/IEC 30134-1standardISO/IEC2016; ed. 2 project (AWI) under waycurrent2026-09-05paidKPI boundaries.↗
ISO/IEC 30134-2standardISO/IEC2026current2026-09-05paidPUE.↗
ISO/IEC 30134-3standardISO/IEC2016current2026-09-05paidRenewable energy factor.↗
ISO/IEC 30134-4standardISO/IEC2017 + Amd 1:2025current2026-09-05paidServer energy efficiency.↗
ISO/IEC 30134-5standardISO/IEC2017 + Amd 1:2025current2026-09-05paidServer utilization.↗
ISO/IEC 30134-6standardISO/IEC2021current2026-09-05paidEnergy reuse factor.↗
ISO/IEC 30134-7standardISO/IEC2023current2026-09-05paidCooling efficiency ratio.↗
ISO/IEC 30134-8standardISO/IEC2022current2026-09-05paidCarbon usage effectiveness.↗
ISO/IEC 30134-9standardISO/IEC2022current2026-09-05paidWater usage effectiveness.↗
EN 50600-4-1standardCENELEC / BSI2016current2026-09-05paidKPI boundaries.↗
EN 50600-4-2standardCENELEC / BSI2016 + A1:2019current2026-10-19paidPUE; A1:2019 aligned it with the 2016 edition of ISO/IEC 30134-2.↗
EN 50600-4-3standardCENELEC / BSI2016 + A1:2019current2026-09-05paidRenewable energy factor.↗
EN 50600-4-6standardCENELEC / BSI2020current2026-09-05paidEnergy reuse factor.↗
EN 50600-4-7standardCENELEC / BSI2020current2026-09-05paidCooling efficiency ratio.↗
EN 50600-4-8standardCENELEC / BSI2022current2026-10-19paidCarbon usage effectiveness.↗
EN 50600-4-9standardCENELEC / BSI2022current2026-09-05paidWater usage effectiveness.↗

4. Open hardware and fabric specifications

An open rack frame does not establish that its power shelf, cooling loop or fabric will work. Pin each interface document, then test the integrated rack in Chapter 7.13 and the transport in Chapter 8.4.

Document identity index: hardware and fabric specifications
DocumentKindIssuing bodyPart / edition / versionStatusAs ofAccessApplicable boundaryEvidence locator
OCP Open Rack V3 Base SpecificationspecificationOCP1.1current2026-09-05freeRack interface.↗
OCP Open Rack V3 HPR V2 72kW Power ShelfspecificationOCPRev 1.0.0 (2026-06-12); Meta contributioncurrent2026-10-17freeIn-rack AC-to-50 V power shelf: 1 OU, six 12 kW PSUs, 60 kW at N+1 on dual 230–277 V cords.↗ · Claim
OCP ORV3 HVDC-LVDC 100kW Power ShelfspecificationOCP1.0.0 (2026-02-20); Meta contributioncurrent2026-10-17freeIn-rack DC-to-48 V shelf for ±400 VDC input: 1 OU, six 18 kW PSUs, 100 kW input.↗
OCP ORW Base SpecificationspecificationOCP1.0.1 (effective 2026-05-05)current2026-10-17freeWide-rack interface.↗
OCP ORW Meta Design SpecificationspecificationOCP1.0.1 (effective 2026-05-05)current2026-10-17freeMeta wide-rack design.↗
OCP ORW Canister IT Gear Design GuideguidelineOCP0.1draft2026-09-05freeIT canister design.↗
OCP ACS Cold Plate RequirementsspecificationOCPRevision 1current2026-09-05freeCold-plate qualification.↗
OCP ACS Cold Plate Cooling Loop RequirementsspecificationOCPRevision 2current2026-09-05freeCooling-loop qualification.↗
OCP Project Deschutes CDU (Data Center Facilities)specificationOCP1.0.0 (effective 2026-02-26)current2026-10-17free2 MW row CDU design (Google contribution): 3 °C approach, 500 GPM, DI water or PG25. Design targets, not a vendor unit's rating.↗
OCP Universal Quick Disconnect (UQD/UQDB)specificationOCPv2.0.0 (effective 2026-09-22)current2026-10-17freeHand-mate and blind-mate liquid couplers, sizes 02–08, single-phase water/glycol; consolidates and stays backward compatible with the v1 UQD and UQDB specifications.↗
OCP MQD/MQDB Design Specification (MGX Quick Disconnect)specificationOCP1.0.0 (Steering Committee approval 2026-10-08; cover misprints 2024)current2026-10-17freeNVIDIA's MGX Quick Disconnect, sizes 02–04, water/glycol: MGX 1.2's busbar coolant connection and fanless I/O bays (trays use UQD 2.0.0). Mates within the MQD family only.↗
OCP Guidelines for Using Propylene Glycol-Based Heat Transfer Fluids in Liquid Cooled RacksguidelineOCPRevision 2.0, v1.0.0 (2026-09-15)current2026-10-17freePG25/PG55 fluid properties, wetted materials, filtration, flushing and in-use limits (Table 14). Replaces the 2022 guidance.↗
OCP Base Specification for Single Phase Water-Based Cold Plate CoolantsspecificationOCPv1.3 (effective 2026-08-06)current2026-10-17freeFresh-fluid limits and certificate of analysis for treated-water cold-plate coolants.↗
OCP Single-Phase Direct-to-Chip Cold Plate Test SpecificationspecificationOCP1.0.0 (effective 2026-09-03)current2026-10-17freeCold-plate qualification tests: leak, pressure decay, burst, thermal resistance, pressure drop, flatness, retention and temperature cycling.↗
OCP Rope Leak Sensor Base SpecificationspecificationOCP1.0.0 (effective 2026-02-02)current2026-10-17freeRope leak sensors: mechanical, signal interface, onboard power, firmware configuration and false-alarm reduction.↗
OCP Mt. Diablo (formerly Diablo 400)specificationOCP1.0.0 (2026-10-08); supersedes v0.7.0current2026-10-16freeSidecar power rack that takes AC and delivers differential 800 VDC (±400 VDC about a midpoint); rated 800 kW to 1.1 MW at 480 VAC.↗ · Claim
OCP Solid State Transformer (SST) SpecificationspecificationOCPRev 0.3.0 (effective 2026-06-22); Google, Microsoft, NVIDIAcurrent2026-10-17freeBlack-box MV-to-800 VDC SST requirements: 5 MW at 13.8 kV, 5/10 MW at 34.5 kV; efficiency, grounding, overload and ride-through.↗ · Claim
OCP DCF Low Voltage Direct Current Power Distribution white paperreportOCP (Data Center Facility, Power Distribution sub-project)v1.1.0 (2026-09-02); v1.0 2026-03-04current2026-10-17freeLVDC distribution up to 1,500 VDC; proposes an 800 VDC voltage band with 840 VDC (U5) as the protection ceiling.↗ · Claim
OCP MGX Accelerated Computing Rack and Trays Design SpecificationspecificationOCPMGX 1.2, revision 1.2.0 (effective 2026-10-06); rev. 1.1 (2024-08-29) is the GB200 NVL72 contributioncurrent2026-10-17freeMGX rack/tray interfaces: ORV3-based 19-inch frame, 48 VDC liquid-cooled busbar to 5,000 A, racks to 250 kW. Excludes power shelves and CDUs; not fully compatible with rev. 1.1.↗ · Claim · Rev. 1.1 · Rev. 1.1 product (GB200 NVL72)
OCP Datacenter NVMe SSD SpecificationspecificationOCPv2.7 (revision 2025-10-24; document dated 2026-01-08); Meta, Microsoft, Google, HPE and Dellcurrent2026-10-17freeHyperscaler requirements for PCIe NVMe SSDs beyond the NVMe standards: media-bytes-written (WAF), latency monitor, telemetry, firmware update; FDP optional (Chapter 9.3, 9.7).↗
OCP CMS Composable Memory Fabric Management Software and APIs ArchitecturespecificationOCPv1.1 (2024-11-14); Seagate contribution to the Composable Memory Systems sub-projectcurrent2026-10-17freeRedfish APIs for composing pooled CXL memory regions from a Composable Memory Appliance; the CMS appliance charter targets under 400 ns round trip (Chapter 9.7).↗ · CMS project
JEDEC JESD328 LPDDR5/5X SOCAMM2 Common StandardstandardJEDEC (JC-45)Version 1.00 (published June 2026)current2026-10-17freeElectrical and mechanical requirements for LPDDR5/5X SOCAMM2 modules used as main memory in data-center and AI servers. Download needs registration.↗
JEDEC JESD270-4 High Bandwidth Memory (HBM4) DRAMstandardJEDECPublished 2025-04-16current2026-10-19freeHBM4 device standard: 2,048-bit interface, 4- to 16-high stacks of 24 or 32 Gb dies (up to 64 GB per stack); Vera Rubin’s memory (Chapter 7.6). Download needs registration.↗
PCI Express Base SpecificationspecificationPCI-SIG7.0 (2025-06-11); the first PCIe 6.0 enterprise SSDs entered volume production in 2026current2026-10-19memberHost I/O link; 7.0 runs 128 GT/s PAM4 with FLIT encoding, up to 512 GB/s bidirectional at x16 (Chapter 9.3).↗
Compute Express Link (CXL) SpecificationspecificationCXL Consortium4.0 (2025-11-18)current2026-10-19freeCache-coherent memory and accelerator attach over PCIe signaling; 3.x added multi-host memory sharing, and 4.0 doubles the rate to 128 GT/s (Chapter 9.7).↗
OCP S.A.F.E. frameworkguidelineOCP1.2 (2025-08)current2026-09-05freeHardware security appraisal.↗
Caliptra specificationspecificationCHIPS Alliance / OCP2.1; main spec v1.0current2026-09-05freeSilicon root of trust.↗
OCP L.O.C.K. (Layered Open-source Cryptographic Key management)specificationOCP (NVMe Project; reference code in CHIPS Alliance Caliptra)1.0 (2025-09); 1.1 at release candidate 4 (effective 2026-06-03)current2026-10-17freeSSD media-encryption-key management on Caliptra: keys isolated from drive firmware; compatible with TCG Opal, Enterprise and Key Per I/O (Chapter 11.5).↗
OCP OBMF-ICP (Open Boot and Management Framework Interface Consolidation Protocol)specificationOCP1.0.0 (2026-10-07); editors Intel and NVIDIAcurrent2026-10-17freeHost-to-BMC sideband (GPIO, I2C, UART, SPI, TPM, IPMI) as channels over one link such as USB; no native encryption, so use an SPDM session or channel protection (Chapter 11.4).↗
OCP RAS API SpecificationspecificationOCPv0.96.0 (2026-10-09), for contribution to OCP; endpoint discovery deferred to the next versiondraft2026-10-17freeVendor-neutral fault management for CPUs, GPUs and accelerators: UEFI CPER error records and CPAD actions over Redfish, PLDM or other transports (Chapter 10.6).↗
UEC Specification 1.0specificationUltra Ethernet Consortium1.0 (2025-06-11)superseded2026-10-19freeFirst public release of the Ethernet transport for AI/HPC.↗ · Claim
UEC Specification 1.1specificationUltra Ethernet Consortium1.1 (2026-10-12)current2026-10-19freeEthernet transport for AI/HPC: Unified Local scale-up profile, in-network collectives, CSIG signaling, programmable congestion control; check which profiles a product supports.↗ · Claim
IBTA InfiniBand Architecture Volume 1specificationIBTARelease 2.1current2026-09-05memberTransport and architecture.↗
IBTA InfiniBand Architecture Volume 2specificationIBTARelease 2.1current2026-09-05memberPhysical links.↗
IEEE 802.3standardIEEE2022current2026-09-05freeEthernet MAC and PHY.↗
IEEE 802.3dfstandardIEEE2024current2026-09-05freeEthernet high-speed PHY amendment.↗
IEEE P802.3djstandardIEEED3.3draft2026-10-11paidNext Ethernet PHY amendment.↗ · Draft access
IEEE 802.1QbbstandardIEEE2011superseded2026-10-19paidPriority flow control. Folded into the 802.1Q bridging standard in 2014; 802.1Q-2022 is the current revision (Chapter 8.6).↗
IEEE 802.1QstandardIEEE2022 (approved 2022-09-21)current2026-10-19freeBridges and bridged networks; since the 2014 revision it carries priority flow control (formerly 802.1Qbb) and ETS (formerly 802.1Qaz) (Chapter 8.6).↗
IEEE 1588standardIEEE2019current2026-09-05paidPacket-network clock synchronization.↗
OCP TAP white paper: Time Synchronization in AI Distributed InfrastructurereportOCP (Time Appliances Project)v0.9.1 (2026-10-01)draft2026-10-17freeWhere shared time helps (observability, latency attribution, time-triggered functions) and where it does not (collective, checkpoint, causal-trace correctness); not a spec.↗
OIF 800ZRspecificationOIFOIF-800ZR-01.0 (2024)current2026-09-05freeCoherent optical interoperability.↗
UALink 200GspecificationUALink Consortium1.0current2026-09-05freeInitial scale-up protocol.↗ · Claim
UALink CommonspecificationUALink Consortium2.0current2026-09-05freeCommon scale-up semantics.↗
UALink 200G DL/PLspecificationUALink Consortium2.0current2026-09-05freeData-link and physical layers.↗
UALink 128G DL/PLspecificationUALink Consortium1.0current2026-09-05freeData-link and physical layers.↗
UALink ChipletspecificationUALink Consortium1.01current2026-09-05freeChiplet integration.↗
OCP Foundation Chiplet System Architecture (FCSA)specificationOCP1.1.0 (effective October 2026; released 2026-10-09); 1.0.0 released 2026-02-10current2026-10-17freeISA-neutral chiplet types and inter-chiplet interfaces, with memory traffic over UCIe 1.1 streaming or BoW; compliance levels 0, 1 and full. Not a PHY or package spec.↗
OCP Bunch of Wires (BoW) PHY SpecificationspecificationOCP2.0 (2023-03-01)current2026-10-17freeOpen die-to-die chiplet PHY: slices, wires, modes and reach. The memory addendum and the transaction/link-layer spec are separate documents.↗
UCIe SpecificationspecificationUCIe Consortium3.0 (2025-08-05)current2026-10-19freeDie-to-die chiplet interconnect; 3.0 adds 48 and 64 GT/s, runtime recalibration and 100 mm sideband reach (Chapter 7.7).↗ · Claim
UALink ManageabilityspecificationUALink Consortium1.0current2026-09-05freeFabric management.↗
OCP ESUN Network Operator Requirements Base SpecificationspecificationOpen Compute Project1.0 (effective 2026-02-09; released 2026-03-10)current2026-10-17freeEthernet scale-up switch/network side; endpoint transport is SUE-T. ESUN 1.1 announced as close, not published.↗
SUE-T (Scale-Up Ethernet Transport) Base SpecificationspecificationOpen Compute Project (contributors Broadcom, Arista)1.0.0 (effective 2026-10-08)current2026-10-17freeScale-up endpoint transport (load/store/atomics over ESUN, UEC UFH or UDP/IP); does not certify any XPU implementation.↗
OCP Open Switch Platform Architecture (OSPA)specificationOpen Compute Project (contributors Meta, Microsoft, Alibaba)Revision 1.0.0 candidate (2026-09-13; 0.9.0 2026-08-06)draft2026-10-17freeSwitch platform management layer: power, hardware access, inventory, thermal, firmware recovery, diagnostics; in OCP Foundation review, not a published OCP spec.↗ · OCP announcement
IEEE P802.1QdwstandardIEEEPAR approved 2022-09-21; no draft produced; withdrawal requested 2026-03-05withdrawal requested2026-10-16unpublishedSource flow control project; no published standard. Successor: P802.1EJ Backward Notification (PAR approved 2026-09-25; ballot draft targeted 2028-07).↗
CSIG Internet-DraftspecificationIndividual authors; IETF Datatrackerdraft-ravi-ippm-csig-01 (2024-02-02)historical2026-10-19freeExpired 2024-08-05; experimental proposal, not an RFC. UE 1.1 (2026-10-12) now includes CSIG congestion signaling.↗
OIF ELSFP 2.0specificationOIFOIF-ELSFP-02.0 (2025-01)current2026-09-05freeExternal laser interface; does not qualify optical-engine FRUs.↗
OIF CMIS (Common Management Interface Specification)specificationOIFOIF-CMIS-05.4 (May 2026)current2026-10-19freeHost-to-module management for pluggable and on-board optics (QSFP-DD, OSFP), including VDM diagnostics such as media-side pre-FEC BER (Chapter 13.7).↗
Open CPX SpecificationspecificationOpen CPX MSA (promoters Ciena, Coherent, Marvell, Molex, Samtec, TeraHop)Rev 1.0 (approved 2026-09-16)current2026-10-17freeCo-packaged/near-package socket and module: 6.4 or 7.2 Tb/s (32 or 36 × 212.5 Gb/s), internal or external laser; modules not expected to be hot-pluggable.↗
UET 1.0.3specificationUltra Ethernet ConsortiumUE 1.0.3 transport layer (2026-07-16); superseded by UE 1.1 (2026-10-12)superseded2026-10-12freeTransport portion of UE specification; profile support separately qualified.↗
TIA 400GBASE-DR4 application overviewreportTIA FOTCUndated; IEEE 802.3bs-2017 applicationcurrent2026-09-05freeFour SMF lanes per direction; eight fibers; application note.↗
TIA 800GBASE-DR8 application overviewreportTIA FOTCUndated; IEEE 802.3df-2024 applicationcurrent2026-09-05freeEight SMF lanes per direction; sixteen fibers; application note.↗
IEEE 802.3bsstandardIEEE2017; incorporated into IEEE 802.3-2022superseded2026-09-05paid200/400 Gb/s Ethernet amendment, including DR4.↗
IEEE P802.3dvstandardIEEEPAR approved 2026-09-25; no draft yetdraft2026-10-16unpublished400 Gb/s per lane signaling: electrical and SMF optical links to 500 m; no published standard.↗

Caliptra supplies a silicon root of trust, and S.A.F.E. supplies third-party design appraisal. Their boundaries are separate; apply them as described in Chapter 11.4 and Chapter 11.3.

July 1, 2028
CIP-002-8 future enforcement date in NERC’s June 2026 bulletin
Apply the version enforceable today and check that the entity and system are in scope. Approval and future enforcement are separate events.
Scope & caveats

Applies only to entities/systems within the standard’s applicability; approval is not the compliance date.

Tenant, data and operator role determine applicability: SOC 2/ISO for commercial operations, FedRAMP/CMMC for relevant US-government work, NERC CIP for applicable registered grid functions, and ISO/IEC 42001 for AI management. Their authorities, scopes and audit duties differ. For OT, IEC 62443-2-1 governs the owner’s security program and IEC 62443-3-2 governs system-design risk assessment. Neither replaces the other. Chapter 11.11 resolves legal applicability. FedRAMP 20x: Classes A–C are available under finalized rules, Class D comes in Phase 4 (est. FY27), and new Rev5 certifications close 11 June 2027.

Document identity index: security and law
DocumentKindIssuing bodyPart / edition / versionStatusAs ofAccessApplicable boundaryEvidence locator
IEC 62443-3-3standardIEC / ISA2013current2026-09-05paidControl-system security requirements.↗
ISO/IEC 27001standardISO/IEC2022 + Amd 1:2024current2026-09-05paidInformation-security management.↗
ISO/IEC 42001standardISO/IEC2023current2026-09-05paidAI management system.↗
EU AI ActregulationEURegulation (EU) 2024/1689current2026-09-05freeAI-system and GPAI obligations.↗
U.S. Copyright Office report on generative AI trainingreportU.S. Copyright OfficeCopyright and Artificial Intelligence, Part 3: Generative AI Training (pre-publication version, 2025-05-09)draft2026-10-19freeUS agency analysis of fair use for AI training data, including acquisition from pirated sources; guidance, not binding law (Chapter 10.10).↗
NIS2regulationEUDirective (EU) 2022/2555current2026-09-05freeCybersecurity duties for in-scope entities.↗
EEDregulationEUDirective (EU) 2023/1791; Delegated Reg. (EU) 2024/1364current2026-10-16freeEnergy efficiency; data centers at ≥500 kW IT must report. Commission adopted rating-scheme act C(2026) 3472 on 2026-09-21; under Parliament and Council scrutiny, not in force.↗ · Delegated Regulation
EnEfGregulationGermanyAct of 13 November 2023 (BGBl. 2023 I No. 309)current2026-10-16freeGerman PUE, ERF and renewable-electricity duties (§11). Amendment bill Drs. 21/8027 (2026-09-16) pending, not enacted.↗
IEC 62443-2-1standardIEC2024; ed. 2.0current2026-09-05paidIACS asset-owner security program.↗
IEC 62443-3-2standardIEC2020; ed. 1.0current2026-09-05paidIACS system-design risk assessment, zones and conduits.↗
BACnet Secure Connect (BACnet/SC)standardASHRAEASHRAE 135-2024 (current; BACnet/SC added by Addendum 135-2016bj, approved 2019-11-18, consolidated in 135-2020)current2026-10-19paidBACnet over WebSockets and TLS with device certificates (Chapter 11.10).↗
Modbus Security ProtocolspecificationModbus OrganizationMB-TCP-Security v36 (2021-07-30)current2026-10-19freeModbus over TLS with X.509v3 certificates, port 802 (Chapter 11.10).↗
NIST SP 800-88guidelineNISTRev. 2 (2025-09); supersedes Rev. 1current2026-10-16freeMedia sanitization methods: Clear, Purge and Destroy (Chapter 14.9).↗
NERC CIP-002standardNERC / FERCCIP-002-5.1a in force; CIP-002-8 enforceable 2028-07-01current2026-10-19freeSorts BES Cyber Systems into high, medium and low impact, which decides how much of CIP-003 to CIP-013 and CIP-015 applies. CIP-014 sets its own scope (Chapter 4.3).↗ · Claim
AICPA SOC 2 (Trust Services Criteria)guidelineAICPA2017 criteria with revised points of focus (2022)current2026-10-19freeAuditor attestation on a service organization’s controls (security, availability, processing integrity, confidentiality, privacy); an opinion, not a certification (Chapter 11.11).↗
FedRAMP (Rev5 and 20x)regulationGSA FedRAMP20x Classes A–C open, Class D in Phase 4; new Rev5 applications close 2027-06-11current2026-10-19freeUS federal cloud-service authorization; 20x assesses automatable Key Security Indicators instead of a control-count package (Chapter 11.11).↗ · Claim
CMMC (32 CFR Part 170)regulationUS Department of WarProgram rule effective 2024-12-16; Phase II third-party certification suspended 2026-07-13current2026-10-19freeCybersecurity levels for defense contractors; Level 2 assesses the 110 NIST SP 800-171 Rev 2 requirements, and Phase I self-assessment still applies (Chapter 11.11).↗ · Claim
NIST SP 800-53guidelineNISTRev. 5, release 5.2.0 (2025-08-27)current2026-10-19freeSecurity and privacy control catalog behind FedRAMP baselines and the SL3/SL5 model-weight proposals (Chapter 11.8).↗
NIST Cybersecurity Framework (CSF)guidelineNIST2.0 (CSWP 29, 2024-02-26)current2026-10-19freeSix functions (Govern, Identify, Protect, Detect, Respond, Recover) for organizing a security program; incident-response guidance SP 800-61r3 maps onto them (Chapter 11.12).↗
EU Cyber Resilience ActregulationEURegulation (EU) 2024/2847current2026-10-19freeProducts with digital elements: exploited-vulnerability and severe-incident reports from 2026-09-11 (24 h, then 72 h); most other duties from 2027-12-11 (Chapter 11.11).↗
ANSSI SecNumCloudcertification schemeANSSI (France)Référentiel v3.2 (2022-03-08)current2026-10-19freeFrench cloud qualification incl. immunity-from-non-EU-law criteria (ch. 19.6) (Chapter 11.11).↗
BSI C5standardBSI (Germany)C5:2026 (final, 2026-03; recommended for audit periods ending on or after 2027-06-01); C5:2020 until thencurrent2026-10-19freeCloud Computing Compliance Criteria Catalogue; required for cloud processing of health/social data under §393 SGB V since 2024-07-01 (Chapter 11.11).↗
EUCScertification schemeENISA / European Commission (Cybersecurity Act)Candidate schemedraft2026-10-19freeEU cloud certification scheme, not adopted; sovereignty criteria dropped in 2024 (Chapter 11.11).↗
MITRE ATT&CKknowledge baseMITREv20.0 (2026-10-13)current2026-10-19freeAdversary tactics and techniques for enterprise IT (Chapter 11.12).↗
MITRE ATT&CK for ICSknowledge baseMITREATT&CK v20.0 (2026-10-13; ICS domain)current2026-10-19freeIndustrial-control-system technique matrix (Chapters 11.10 and 11.12).↗
MITRE ATLASknowledge baseMITREData release v2026.09 (2026-09-15)current2026-10-19freeAdversarial Threat Landscape for Artificial-Intelligence Systems: attacks on models and training pipelines (Chapter 11.12).↗
May 2024
TIA-942-C: AI growth and sustainability; Rated-1..4 naming dates to the 2014 TIA/Uptime separation
Scope & caveats

TIA announced Revision C on May 9, 2024. Rated terminology predates this edition; TIA/Uptime announced the Tier-name separation in March 2014. Licensed clause-level conformance and local adoption require separate records.

5th ed. (2021)
ASHRAE fifth edition: W17/W27/W32/W40/W45/W+; new W40 and H1
Scope & caveats

The fifth edition revised an existing liquid-class scheme; liquid classes W1–W5 predate it. The same edition adds the H1 air class (15–25 °C allowable, 18–22 °C recommended).

1.0.0
OCP Mt. Diablo: 1.0.0 since 2026-10-08 (renamed from Diablo 400), replacing v0.7.0; power racks of 800 kW to 1 MW+
Scope & caveats

Final 1.0.0 base specification, renamed from Diablo 400. It supersedes v0.5.2 (May 2025) and v0.7.0 (March 2026). Scope is 800 kW to 1 MW+ per power rack, which can be paralleled; Table 5 gives 800 kW–1.1 MW at 480 VAC and up to 718 kW at 400 VAC.

Chapter 0.4 covers how to bring a standard into a project. Related chapters: resilience in Chapter 0.5; DLC in Chapter 5.4; heat reuse in Chapter 5.9; water accounting in Chapter 15.4; DC power in Chapter 4.7; grid-asset scope in Chapter 4.3.
Cite this chapter
Fehn, J. (2026). Standards & Specifications Cross-Reference Matrix (Chapter A). The Definitive Guide to AI Data Centers. https://aidatacenterguide.com/appendix-appendices-and-reference-data/a-standards-and-specifications-cross-reference-matrix (accessed 2026-10-25).
@misc{aidc-A,
  author       = {Fehn, Jacob},
  title        = {Standards & Specifications Cross-Reference Matrix (Chapter A)},
  howpublished = {The Definitive Guide to AI Data Centers},
  year         = {2026},
  url          = {https://aidatacenterguide.com/appendix-appendices-and-reference-data/a-standards-and-specifications-cross-reference-matrix},
  note         = {Accessed 2026-10-25}
}
Spotted an error? Suggest an edit