OCP Mt. Diablo Disaggregated Power Rack Specification (formerly Diablo 400): current release
1.0.0observed
| Value kind | observed — Reported measurements, counts, and specifications keep the precision and scope stated by their source; an exact specification is not treated as a range. |
|---|---|
| Scope | Final 1.0.0 base specification, renamed from Diablo 400. It supersedes v0.5.2 (May 2025) and v0.7.0 (March 2026). Scope is 800 kW to 1 MW+ per power rack, which can be paralleled; Table 5 gives 800 kW–1.1 MW at 480 VAC and up to 718 kW at 400 VAC. |
| As of | October 8, 2026 |
| Source | OCP, Mt. Diablo Disaggregated Power Rack Specification 1.0.0 (Microsoft, Meta, Google), base specification effective 2026-10-08 · Cover; version history (1.0.0: final release, renamed from Diablo 400); section 5 scope; Table 5 |
| Review | checking…review by 2027-04-08 · standard cadence |
| Recorded changes | last 2026-10-16 · 3 revisions tracked |
| Claim id | ocp-diablo-400-mt-diablo-sidecar-power-spec-400 |
Where the guide uses it
- 0.4 The Standards & Specifications Landscape (Living Index)
- A Standards & Specifications Cross-Reference Matrix
← Full numbers register — every date-stamped figure in the guide, with revision history.