UPS efficiency: double-conversion vs bypass-ECO / active high-efficiency mode

94-97% → 98-99%observed

Value kindobserved — Reported measurements, counts, and specifications keep the precision and scope stated by their source; an exact specification is not treated as a range.
ScopeBypass-style ECO (inverter on standby, short break on transfer) and active high-efficiency modes (inverter energized, conditioning held, uninterrupted transfer) are different products that both reach ~98-99%. Contemporary double-conversion designs reach ~97%, so the recoverable delta is product- and load-dependent — take it from measured efficiency curves and acceptance tests, not from the mode name.
As of2013-01 / 2020-01
SourceVertiv Liebert EXL S1 UPS datasheet SL-26095 (R01/20): double-conversion (VFI) up to 97%, ECO/VFD above 99%, Dynamic Online up to 99%. The 94% lower bound is The Green Grid's typical double-conversion figure (Jan 2013 Eco Mode white paper). · Datasheet page 2, Typical Functioning Modes; Green Grid Eco Mode white paper (Jan 2013) for typical 94% VFI versus 98% Eco Mode
Reviewchecking…review by 2027-10-16 · standard cadence
Recorded changeslast 2026-10-16 · 4 revisions tracked