EKPC transmission-connected load power-factor range, Facility Connection Requirements Rev. 16 §9.0

0.95 lagging–0.98 leadingobserved

Value kindobserved — Reported measurements, counts, and specifications keep the precision and scope stated by their source; an exact specification is not treated as a range.
ScopeA named utility example for connected loads; the host utility's requirements and tariff set the site duty. This is not the separate generator capability range in §9.1.
As of2025-08-15
SourceEast Kentucky Power Cooperative, Facility Connection Requirements, Rev. 16, effective August 15, 2025 · §9.0, p.37
Reviewchecking…review by 2027-04-17 · standard cadence
Recorded changeslast 2026-10-19 · 2 revisions tracked
Claim idtypical-power-factor-obligation-at-the-poi-for