Concentrated (point) design load for one Tate ConCore 1000 access-floor panel on Tate's own understructure

1,000 lb concentrated design loadobserved

Value kindobserved — Reported measurements, counts, and specifications keep the precision and scope stated by their source; an exact specification is not treated as a range.
ScopeThis rating covers one Tate panel under Tate's own test and permanent-set criterion; it is not a rack rating. Concentrated, rolling and distributed ratings are separate. A rack's weight is shared among its feet or casters and the floor system, so compare the OEM foot and wheel reactions with the whole panel, pedestal, stringer, slab and move route.
As ofTate datasheet 2025-10-30
SourceTate ConCore 1000 Bare Panel-24 inch datasheet, ECN 16502
Reviewchecking…review by 2027-04-01 · standard cadence
Recorded changeslast 2026-10-14 · 4 revisions tracked
Claim idtypical-legacy-raised-floor-rating-vs-a-3-000

Where the guide uses it

← Full numbers register — every date-stamped figure in the guide, with revision history.