reference supply temperature of a conventional (3rd-generation) district-heating network; 4th-generation networks typically run about 50–70 °C

80–100 °Cestimate

Value kindestimate — Interpret this value according to its displayed kind, scope, source, and as-of date.
ScopeReference values, not a design constant: the network's actual seasonal schedule decides what a data center can feed. IEA DHC STEP uses 80/40 °C as its conventional reference pair and 55/25 °C for low-temperature networks, with 60/35 °C the step at which server waste heat becomes directly usable. A warm-water DLC return (45–60 °C) still needs a heat-pump lift for most networks; direct delivery works only where the return, less the exchanger approach, meets the network's supply temperature.
As of2017 IEA DHC reference
SourceIEA DHC Annex TS1 Final Report (2017), §4.1; Yuan et al., Renewable and Sustainable Energy Reviews 219, 115863; IEA DHC Annex XII STEP final report
Reviewchecking…review by 2027-03-01 · standard cadence
Recorded changeslast 2026-10-16 · 4 revisions tracked
Claim idsupply-temperature-a-conventional-3g-district