Component importance factor Ip = 1.5 for life-safety-critical components, components meeting the adopted ASCE 7 hazardous-substance criteria, and components in or attached to a Risk Category IV structure that are needed for continued operation or whose failure could impair it; otherwise Ip = 1.0

Ip = 1.5 (scoped)observed

Value kindobserved — Reported measurements, counts, and specifications keep the precision and scope stated by their source; an exact specification is not treated as a range.
ScopeIp is assigned according to the component’s function and failure consequences, not categorically to every component in every data center. It is distinct from the structural seismic importance factor Ie.
As of2026-10
SourceNational Institute of Standards and Technology, NIST GCR 23-037 (January 2023) · Section 2.3.3 and Table 2-2, pp. 48–49; Section 3.3.3, pp. 85–86
Reviewchecking…review by 2027-10-01 · standard cadence
Recorded changeslast 2026-10-15 · 3 revisions tracked
Claim idseismic-importance-factor-for-data-centers-as

Where the guide uses it