Advanced Energy ORV3 HPR power shelf, 50 V nominal: 33 kW at N+0 (six 5.5 kW modules), 27.5 kW at module N+1 per shelf, and 16.5 kW at N+N for the dual-whip configuration
33 kWobserved
| Value kind | observed — Reported measurements, counts, and specifications keep the precision and scope stated by their source; an exact specification is not treated as a range. |
|---|---|
| Scope | Rating of one first-generation HPR shelf. At full load the shelf's default output is 49 V, about 674 A; the 660 A figure at 50 V nominal is an illustration. Compare shelf DC output with the rack's DC load, not its AC input rating. Not the ORv3 ceiling: OCP's HPR V2 shelf spec (Meta, 1.0.0, 2026-06-12) defines a 72 kW shelf, 60 kW at N+1. |
| As of | 2026-10 |
| Source | Advanced Energy, 50 V 33 kW 1OU ORV3 HPR power shelf datasheet, October 2026 · pp. 1-2: redundancy ratings, 49-50 V droop and 674 A maximum |
| Review | checking…review by 2027-04-13 · standard cadence |
| Recorded changes | last 2026-10-13 · 2 revisions tracked |
| Claim id | ocp-orv3-hpr-power-shelf-output-6-5-5-kw |
Where the guide uses it
← Full numbers register — every date-stamped figure in the guide, with revision history.