HPE GB200 NVL72 secondary-loop design flow, guide heat-balance derivation for its ~115 kW liquid load at OCP's 7.5–12 °C cold-plate rise

~140–220 L/min (water); ~144–230 L/min PG25derived

Value kindderived — Derived values are guide calculations; their result is only as fixed as the stated inputs, scope, and method.
ScopeGuide water-property heat balance at OCP's 7.5–12 °C rise; a design illustration, not an OEM flow requirement. The PG25 band applies OCP's 1.25–2.0 L/min per kW. The separate QCT 45 °C inlet and 65 °C return maxima do not prescribe this rise.
CaveatThe operating flow must also satisfy the selected rack and CDU pressure/flow operating limits.
As of2026-10
SourceHPE GB200 NVL72 data sheet (PSN1014890104MYEN, October 2026), p.2: 132 kW total, 115 kW liquid, 17 kW air; OCP OAI System Liquid Cooling Guidelines §1.3 (2023-03-03 update) for the 7.5–12 °C rise and PG25 flow rule; guide water-property calculation. · HPE PDF p.2, Advanced Direct Liquid Cooling from HPE; OCP OAI guidelines §1.3 (printed p. 7); guide Q = mass flow × heat capacity × temperature rise
DerivationWater at 1.00 kg/L and 4.18 kJ/(kg·K): 115 × 60/(4.18 × 12) = 137.6 L/min, rounded to ~140; 115 × 60/(4.18 × 7.5) = 220.1 L/min, ~220. PG25 at OCP §1.3's 1.25–2.0 L/min per kW: 115 × 1.25 = 143.75 ≈ 144; 115 × 2.0 = 230 L/min. Use the approved formulation's properties for the glycol actually supplied.
Reviewchecking…review by 2026-12-22 · standard cadence
Recorded changeslast 2026-10-19 · 5 revisions tracked
Claim idnvl72-coolant-flow-guide-derivation-1-25-2-0-l