The Definitive Guide toAI Data Centers
Ask the GuideAboutAccount
Guide › Numbers register › Claim

OCP Mt. Diablo 1.0.0 specifies differential 800 VDC: +400 V and −400 V around a midpoint bonded to PE through high resistance or solidly.

±400 VDCobserved

Value kindobserved — Reported measurements, counts, and specifications keep the precision and scope stated by their source; an exact specification is not treated as a range.
ScopeNominal ±400 V about the midpoint, 800 V full span. High-resistance and solid midpoint grounding have different fault responses, and both need a ground-fault detector (§8.1.4.2.3). Component sourcing does not qualify the installation.
As of2026-10-08
SourceOCP, Mt. Diablo Disaggregated Power Rack Specification 1.0.0 (Microsoft, Meta, Google), base specification effective October 8, 2026 · §7.3.1 Table 4 (+400 and −400 VDC to COM; 800 VDC to 0/RTN); §8.1.4.1 (midpoint grounding: high resistance or solid).
Reviewchecking…review by 2027-10-08 · standard cadence
Recorded changeslast 2026-10-16 · 3 revisions tracked
Claim idmt-diablo-diablo-400-bipolar-rail-chosen-to

Where the guide uses it

← Full numbers register — every date-stamped figure in the guide, with revision history.