Intel D50DNP facility-supply coolant dew-point margin (primary loop; platform-specific requirement)

≥2 °C above dew pointobserved

Value kindobserved — Reported measurements, counts, and specifications keep the precision and scope stated by their source; an exact specification is not treated as a range.
ScopeAn Intel D50DNP requirement for the primary-loop facility supply, not a default for secondary-supply CDUs or the industry. Work out the installed secondary-loop margin from the equipment limits plus the sensor, control and reserve allowances.
As of2024-07
SourceIntel Server D50DNP Family Technical Product Specification Rev. 1.4, July 2024, Table 33, p. 92, primary-loop row and note 1 · Table 33, p. 92: facility supply coolant temperature (primary loop), note 1
Reviewchecking…review by 2027-10-14 · standard cadence
Recorded changeslast 2026-10-14 · 4 revisions tracked
Claim idminimum-secondary-supply-margin-cdus-hold-to

Where the guide uses it