IEEE 519-2022 Table 2 limit on current distortion (TDD) at the PCC for systems from 120 V through 69 kV; the Isc/IL short-circuit ratio sets the row

5–20% TDDobserved

Value kindobserved — Reported measurements, counts, and specifications keep the precision and scope stated by their source; an exact specification is not treated as a range.
ScopeTable 2 covers PCC voltages from 120 V through 69 kV only. Table 3 applies above 69 kV through 161 kV and Table 4 above 161 kV, and both are tighter. Table 1 holds the voltage THD limits. Use the row for your actual PCC voltage and Isc/IL.
As of2022
SourceIEEE Std 519-2022, Tables 1-4 (IEEE Standards Association) · Table 2: current distortion limits for systems rated 120 V through 69 kV; TDD runs from 5% to 20% by Isc/IL
Reviewchecking…review by 2027-02-06 · slow cadence
Recorded changeslast 2026-10-13 · 3 revisions tracked
Claim idieee-519-current-distortion-tdd-limit-at-the