Illustrative steady-state fault-current limit of grid-following inverters, against 5-10x for synchronous machines. The inverter's controls decide how protection responds.

~1.2–1.5xestimate

Value kindestimate — Interpret this value according to its displayed kind, scope, source, and as-of date.
ScopeAn illustrative range for grid-following inverters, not a universal inverter limit. The same presentation shows 2–3 p.u. for some grid-forming voltage-regulation schemes. Get the offered device's phase, sequence and time-dependent fault response.
As of2021-06
SourceSandia National Laboratories, M. J. Reno, Controls and Fault Response of Inverter-Based Resources, SAND2021-7782C · slide 4, Inverter Short-Circuit Models