Guide footprint-average screening range for 3,000–3,300 lb over approximately 0.64 m²

~435-480 psfderived

Value kindderived — Derived values are guide calculations; their result is only as fixed as the stated inputs, scope, and method.
ScopeThe class-mass endpoints are screening assumptions, not HPE minimum and maximum ratings. HPE's GB200 QuickSpecs give a separate 3,245 lb filled-rack figure. Neither result is a support, rolling or uniform floor rating.
As of2026-09
SourceHPE GB200 QuickSpecs V6, September 8, 2026: system dimensions and loaded-with-fluid mass; the guide range uses its own class-mass screening assumptions. · System Unit Specifications; an OEM example inside the guide's screening range
Derivation3,000–3,300 lb divided by approximately 0.64 m² / 0.09290304 m² per ft² gives approximately 435–480 psf. Footprint area is not allocated structural-bay area.
Reviewchecking…review by 2027-03-08 · standard cadence
Recorded changeslast 2026-10-19 · 5 revisions tracked
Claim idback-calculated-nvl72-footprint-loading-3-000-3

Where the guide uses it