Vertiv Liebert CRV chilled-water in-row units: net sensible cooling capacity per unit

27.1 / 46.3 / 53.2 kW per CW unitobserved

Value kindobserved — Reported measurements, counts, and specifications keep the precision and scope stated by their source; an exact specification is not treated as a range.
ScopeCR032, CR040 and CR050 respectively, at 95 F return dry bulb and 23% RH; CR032 and CR040 at 45/55 F entering/leaving water, CR050 at 55/68 F. The CR035 DX and water/glycol variants have separate schedules. Converting a per-unit duty into kW per rack depends on the number of units serving the row, airflow distribution, containment and the redundancy case. It is not a rating for a close-coupled fan wall.
As of2025-05
SourceVertiv · Vertiv Liebert CRV SL-71133 R05/25, p. 4, chilled-water schedule
Reviewchecking…review by 2027-10-14 · standard cadence
Recorded changeslast 2026-10-14 · 3 revisions tracked
Claim idactive-in-row-cooler-capacity-per-rack